| Technical data
|
|
| Output power
|
1500 VA, 1050 W
|
| Back up time
|
Only 230 VAC
100 % load, 5 min. / 80 % load, 7 min. / 50 % load, 15 min.
|
|
|
Only 24 VDC
100 % load, 25 min. / 80 % load , 30 min. / 50 % load, 50 min.
|
| Overload protection
|
Switch off with auto-recovery
|
| Charging time
|
App. 4 h charged up to 80 %
|
|
|
| Input
|
|
| Input voltage range
|
160…276 VAC at 100 % load
|
| Derating
|
70 % load at 140…159 VAC, 40 % load at 120…139 VAC
|
| Input frequency range
|
50 or 60 Hz ±3 Hz (automatic frequency recognition)
|
| Input current with charged batteries
|
5.7 A
|
| Input current
|
8 A (at rated load, minimum input voltage and battery charging)
|
| Inrush current behaviour
|
Softstart
|
| Power factor (cos j)
|
>0.97
|
|
|
| Output AC
|
|
| Output voltage
|
AC: 230 VAC, adjustable 208, 220, 230, 240 VAC
|
| Output frequency
|
50 / 60 Hz ±0.5 %
|
| Output voltage tolerance
|
±2 %
|
| Efficiency at rated load
|
>90 %
|
| Overload
|
125 % for 1 min., 150 % for 10 sec.
|
| Short circuit protection UPS
|
Switch off of UPS or fuse at input line
|
| Wave form in UPS mode
|
Sine wave
|
| Power factor
|
0.7
|
|
|
| Output DC
|
|
| Output voltage
|
DC: 24 VDC / 10 A, other voltages and powers on request
|
| Overvoltage protection
|
Switch off at +26 V…31 V
|
| Short circuit protection
|
Switch off with auto-recovery
|
| Load regulation
|
±1 %, load step ±40 % related to 60 % load
|
|
|
| Bypass
|
|
| Voltage tolerance
|
160…276 VAC
|
| Frequency tolerance
|
±5 Hz
|