UPSI-B-2410
24 VDC/10 A
- Battery monitoring
- Online technology
- Battery pack BP-2425C also for -30…+70 °C!
The UPSI-B-2410 buffers DC supplied systems in ambient temperatures where other UPS fail. Adequate batteries are included. Online technology guarantees interrupt-free power. Micro-processor controlled charging and an active battery check provides a long battery life. Typical application areas are automation and automotive.
| Technical data
|
|
| Input voltage
|
24 VDC (22…36 V)
|
| Input current
|
12.5 A max.
|
| Output voltage
|
Normal mode: app. 0.4 V below input voltage
Battery mode: app. 30.9…19 VDC
|
| Output current
|
10 A max.
|
| Battery charge current
|
2 A max. (internal battery charger)
|
| Charging voltage
|
26.4…31.2 V, temperature-controlled
|
| Discharge protection of battery
|
19 VDC ±2 %
|
| Battery low
|
<21 V ±2 % (Battery mode)
|
| Transfer time / transfer limits
|
0 ms, online technology, Main / BAT 20 V /, BAT / Main 22 V
|
| Back up time
|
See datasheet of battery pack BP-2425C
|
| Interface
|
DSUB9 female, open collector, potential-free for
Outputs: power fail, battery low, Input: Shutdown
Optionally also with UPS software for connecting all established operating systems
|
| Type of battery
|
Maintenance-free pure lead-tin battery (PLT)
|
| Safety / EMC
|
CE
|
| Operating temperature
|
-30…+70 °C
|
| Storage temperature
|
-40…+80 °C
|
| Operating humidity
|
0…95 % RH, non-condensing
|
| Dimensions (WxDxH)
|
152 x 103 x 75 mm ±0.5 mm
|
| Weight (net)
|
0.75 kg
|
| LED display
|
3 colour LED for “Power ok” (green), “Power Fail” (orange), “Battery low” (red/orange flashing) and “Battery defect” (red/green flashing)
|
| Battery monitoring
|
Battery test is carried out every 10 minutes in normal mode
|
| Power consumption
|
App. 150 mA
|
| Operating height
|
Max. 12000 feet above sea level
|
| Shutdown Suppression
|
The Shutdown signal is disabled for about two minutes after startup.
|
| Reboot function
|
If DC IN fails and main power returns during shutdown mode of Windows®, the operating system will ‘lock’ with the message “Your PC is now safe”. The reboot function restarts the system after about 5 seconds.
|