UPSI-2402-IP
24 VDC/5A
- Outdoor UPS
- Protection class IP67
- Robust aluminium casing
The new DC-UPS UPSI-2402-IP has been designed for outside use. The robust casing protects electronic parts according to protection class IP67 against intrusion of water, dust and dirt. The μC-controlled DC-UPS is provides with various protective functions and a battery control. In case of a supply voltage failure, the battery-capacity is sufficient to ensure the necessary supply to the user. Additionally, the UPSI-2402-IP is equipped with a load sensor and a timer function.
| Technical data
|
|
| Input voltage
|
24 VDC (22.5…30 V)
|
| Input current
|
5.5 A max.
|
| Output voltage
|
In normal mode: app. 0.5 V below input voltage
In battery mode: app. 27…19 VDC
|
| Output current
|
5 A max.
|
| Battery charge current
|
0.4 A max. (internal battery charger)
|
| Charging method
|
UI characteristic, with temperature regulation
|
| Protection
|
Deep discharge protection: 19 VDC ±2 %
Overload protection at output: 10 A for 2 seconds, switch off
Short-circuit protection: Switch off
|
| Transfer time / limits
|
Mains / battery 20 VDC ±2 %, Battery / mains 22 VDC ±2 %
|
| Interface
|
DSUB9 connector, female (at interface cable)
Outputs: Power Fail, Battery Low     Input: Shutdown
Optionally also available with UPS software for connection to common operating systems
|
| Type of battery
|
Equipped lead-gel-battery, maintenance-free, 1.3 Ah
|
| Safety / EMC
|
CE
|
| Operating temperature
|
0…+40 °C
|
| Storage temperature
|
-10…+40 °C
|
| Storage humidity
|
0…95 % RH, non-condensing
|
| Dimensions (WxDxH)
|
178,5 x 160 x 85 ±0.5 mm
|
| Weight (net)
|
2.7 kg
|
| Battery monitoring
|
Battery test is carried out in normal mode approx every 10 minutes (optional sginaling contact)
|
| Power consumption
|
App. 50 mA
|
| Shutdown suppression
|
During system start-up the shutdown signal is suppressed for app. 2 minutes
|
| Reboot function
|
If power fails and then returns during the shutdown mode of Windows®, the operating system will ‚lock‘ with the message „Your PC is now safe“. The reboot function restarts the system after about 10 seconds.
|
| Load sensor
|
Switch-off in UPS mode <10 Watt
|
| Timer function
|
2 min – 6 min – 20 min – off, adjustable via DIP switch
|
| Back up time
|
App. 30 min at 1 A / app. 8 min at 3 A / app. 3 min at 5 A (measured at +20 °C)
|
| Optional accessories |
Article-No. |
Designation |
|
| RUPS 2000-B1 |
UPS Management Software (CD-ROM) |
link to the product |