UPSI-2402

24 V/5 A

  • Continuous battery monitoring
  • Timer function
  • PC interface

The newly designed DC UPS UPSI-2402 protects connected consumer loads from supply voltage fluctuations and interruptions. The μC controlled DC UPS provides various protections. Among the most important is the continuous battery monitoring feature. This ensures that sufficient capacitance remains in the battery to guarantee the supply of consumer loads in case of power failure. New features of the UPSI-2401 are a load sensor and a timer function. The timer function was integrated and allows a timer-controlled switch-off of the UPS.

Technical data

 

Input voltage

24 VDC (22.5…30 V)

Input current

5.5 A max.

Output voltage

In normal mode: app. 0.5 V below input voltage
In battery mode: app. 27…19 VDC

Output current

5 A max.

Battery charge current

0.4 A max. (internal battery charger)

Charging method

UI characteristic, with temperature regulation

Protection

Deep discharge protection: 19 VDC ±2 %
Overload protection at output: 10 A for 2 seconds, switch off
Short circuit protection: Switch off

Transfer time / limits

Mains / battery 20 VDC ±2 %, Battery / mains 22 VDC ±2 %

Interface

DSUB9 connector, female
Outputs: Power Fail, Battery Low     Input: Shutdown
Optionally also available with UPS software for connection to common operating systems

Type of battery

2x Battery pack BP-1225, maintenance-free, 12 V / 2.5 Ah (recommended)

Safety / EMC

CE

Operating temperature

-20…+70 °C

Storage temperature

-40…+80 °C

Storage humidity

0…95 % RH, non-condensing

Dimensions (WxDxH)

100 x 120 x 24.7 mm ±0.5 mm

Weight (net)

2 kg

Product-specific data

LED display

3-colour-LED for „Power ok” (green), „Power Fail” (orange), „Battery low” (red/orange flashing) and „Battery defect” (red/green flashing), short circuit at output/overload (red)

Battery monitoring

Battery test is carried out in normal mode approx every 10 minutes, in case of “Battery defect“ notification the LED flashes red/green (optional sginaling contact)

Power consumption

App. 50 mA

Shutdown suppression

During system start-up the shutdown signal is suppressed for app. 2 minutes.

Reboot function

If power fails and then returns during the shutdown mode of Windows®, the operating system will ‚lock‘ with the message „Your PC is now safe“. The reboot function restarts the system after about 5 seconds.

Load sensor

Switch-off in UPS mode <10 Watt

Timer function

2 min – 6 min – 20 min – off, adjustable via DIP switch

Back up time

App. 1 h 45 min at 1 A  /  app. 30 min at 3 A  /  app. 15 min at 5 A (measured at +21 °C)

Optional accessories

Article-No.

Designation

BP-1225 Battery pack, 12 V / 2.5 Ah, -30…+70 °C (2 peaces needed) link to the product
LC-R121R3PG Battery for UPSI-2402, 12V / 1.3 Ah, 0…40 °C (2 pieces necessary) link to the product
RUPS 2000-B1 UPS Management Software (CD-ROM) link to the product
CB-RS-020 Interface cable, 9-pole link to the product