BP-2450C

24 V/5 Ah

  • Temperature range -30…+70 °C
  • Service life up to 15 years
  • Temperature sensor

The high-quality battery pack BP-2450C serves to store energy for DC UPS models of the UPSI-B-24xx series. The equipped CYCLON cells are distinguished by their wide ambient operating temperature range from -30…+70 °C. The service life of CYCLON cells with up to 15 years is considerably higher as compared to conventional lead-acid batteries. To ensure maximal performance the charging voltage is controlled by a temperature sensor.

Technical data

 

Nominal voltage

24 VDC

Capacitance

5 Ah

Number of batteries

12 cells à 2 V

Type of battery

Maintenance-free CYCLON batteries

Life cycles

10 000…300 depending on ambient temperature, charge and discharge

Fuse

50 A, circuit breaker

Operating temperature

-30…+70 °C

Storage temperature

-30…+70 °C

Temperature sensor

For use with UPSI-B-24xx series

Dimensions

268 x 102 x 140 mm, ±0.5mm

Weight (net)

6.7 kg

Back up time measured at +21 °C by means of UPSI-B-2410

Discharge current

1 A

5 A

10 A

Time app.

4 h 50 min

48 min

21 min

The Back up time depends on battery capacity, load and ambient temperature.

Technical documentation:
© 2008-2012  |  BICKER ELEKTRONIK GmbH - Ludwig-Auer-Straße 23 - 86609 Donauwörth (DE)