BS17A/H24/2.0L
24 V/2.0 Ah
- Battery pack for PCFD-180-X2S / PCFL-180-X2S2
- NiMH battery
- Installation into 3.5“ drive slot
The NiMH battery pack BS17A-H24/2.0L serves to store energy for the UPS PC power supplies PCFD-180-X2S / PCFL-180-X2S2. Due to the higher energy density of the maintenance-free nickel metal hydride cells back-up time is increased considerably – moreover, they weigh much less as compared to lead batteries. The NiMH battery pack is designed for installation into the 3.5“ drive slot of a computer. A pin-and socket connector is provided for connection to the UPS PC power supply.
| Technical data
|
|
| Voltage
|
24 VDC
|
| Capacitance
|
2.0 Ah
|
| Battery type
|
NiMH battery, 9.6 VDC, in UPS mode 18 VDC via booster
|
| Output power
|
97.2 W (18 VDC / 5.4 A)
|
| Peak power (5 Sec.)
|
0 °C / 80 W, +5 °C / 100 W, +10 °C / 110 W, +15 °C / 120 W, +20 °C / 130 W
|
| Backup time of a typical PC
|
100 W app. 5 minutes, 50 W app. 11 minutes
|
| Fuse
|
30 A
|
| Charge current
|
0.2 A (15 h max.), internal charger
|
| Operating temperature
|
0…+45 °C
|
| Derating
|
0…+5 °C, 78 W
|
| Storage temperature
|
-20…+30 °C, storage possible 1 year or less
-20…+40 °C, storage possible 90 days or less
-20…+50 °C, storage possible 30 days or less
|
| Dimensions (WxDxH)
|
101.5 x 180 x 25 mm ±0.5 mm
|
| Weight (net)
|
0.9 kg
|
| Optional accessories |
Article-No. |
Designation |
|
| RUPS 2000-B1 |
UPS Management Software (CD-ROM) |
link to the product |
| WH-02VH02VH-250 |
Battery connector cable for BS17A-H24/2.0L, length 250 mm |
link to the product |
| WH-S1004-500-02 |
Interfacecable for BS17A-H24/2.0L, length 500 mm |
link to the product |
Technical documentation:
|