UPSI-B-2405
24 V/5 A
- Operating temperature -30…+70 °C
- Reboot function
- Monitoring interface
The UPSI-B-2405 buffers DC supplied systems by online technology via an intermediate DC link, which guarantees interrupt-free power for DC consumers loads with short hold times. An interface for connection to the operating system of the computer is provided. With the “Reboot” function the UPSI-B-2405 features an integrated auto-recovery routine to ensure a restart after a shut-down of the computer was initiated.
| Technical data |
|
|---|---|
| Input voltage |
24 VDC (20…36 V) |
| Input current |
7 A max. |
| Output voltage |
Normal mode: app. 0.4 V below input voltage |
| Output power |
120 Watt |
| Battery charge current |
1 A max. (internal battery charger) |
| Charging voltage |
26.4…30.9 VDC, depending on temperature |
| Protection |
Discharge protection of battery: 19.5 VDC ±2 % |
| Transfer time / transfer limits |
0 ms |
| Back up time |
Depending on battery capacitance and load |
| Interface |
DSUB9 female, open collector, potential-free for |
| Battery type |
Maintenance-free lead tin battery (Hawker Cyclon) |
| Operating temperature |
-30…+70 °C |
| Dimensions (WxDxH) |
100 x 68 x 40 mm, ±0.5 mm |
| Weight (net) |
0.2 kg |
| Product-specific data |
|---|
| Switch over voltage |
Normal mode to battery mode 20 VDC ±2 %, measured at minimum load of 0.5 A |
| Inverse-polarity protection / input |
Fuse 7.5 A (must be provided on-site by customer) |
| Inverse-polarity protection / battery |
Fuse 7.5 A (at battery pack BP-2425) |
| Software (optional) |
UPS software RUPS2000 OEM, for all established operating systems |
| LED display |
3 colour LED connector for: Power ok (green) / Power Fail (orange) / Battery Low (red / orange flashing) / Battery defect (red / green flashing) |
| Battery capacitance |
24 V / 2.5 Ah, recommended Battery pack , BP-2425 or BP-2425C |
| Battery monitoring |
Battery test is carried out every 10 minutes in normal mode |
| Shutdown-Suppression |
The Shutdown signal is disabled for about two minutes after startup, because a possible interface test of Windows® combined with a mains failure at the same time would switch the module off. |
| Reboot function |
If DC IN fails and main power returns during shutdown mode of Windows®, the operating system will ‘lock’ with the message “Your PC is now safe”. The reboot function restarts the system after about 5 seconds (operator intervention not required). |
| Power consumption |
App. 100 mA |
| Optional accessories | ||
Article-No. |
Designation |
|
|---|---|---|
| BP-2425-05 | Battery pack 24 V / 2.5 Ah, -30…+70 °C | link to the product |
| BP-2412A | Battery pack, 24 VDC/1.2 Ah / 0…+40 °C | link to the product |
| RUPS 2000 OEM | UPS software bundle | link to the product |