You are here: Bicker Elektronik / Products / UPS systems / DC UPS / UPSI-B-2405

UPSI-B-2405

24 V/5 A

  • Operating temperature -30…+70 °C
  • Reboot function
  • Monitoring interface

The UPSI-B-2405 buffers DC supplied systems by online technology via an intermediate DC link, which guarantees interrupt-free power for DC consumers loads with short hold times. An interface for connection to the operating system of the computer is provided. With the “Reboot” function the UPSI-B-2405 features an integrated auto-recovery routine to ensure a restart after a shut-down of the computer was initiated.

Technical data

 

Input voltage

24 VDC (20…36 V)

Input current

7 A max.

Output voltage

Normal mode: app. 0.4 V below input voltage
Battery mode: app. 30.9…19.5 VDC

Output power

120 Watt

Battery charge current

1 A max. (internal battery charger)

Charging voltage

26.4…30.9 VDC, depending on temperature

Protection

Discharge protection of battery: 19.5 VDC ±2 %
Overvoltage protection: From >32 VDC the UPSI-B-2405 switches to battery mode to protect the downstream consumer loads

Transfer time / transfer limits

0 ms

Back up time

Depending on battery capacitance and load

Interface

DSUB9 female, open collector, potential-free for
Outputs: Power fail, battery low Input: Shutdown

Battery type

Maintenance-free lead tin battery (Hawker Cyclon)

Operating temperature

-30…+70 °C

Dimensions (WxDxH)

100 x 68 x 40 mm, ±0.5 mm

Weight (net)

0.2 kg

Product-specific data

Switch over voltage

Normal mode to battery mode 20 VDC ±2 %, measured at minimum load of 0.5 A
Battery mode to normal mode 22 VDC ±2 %, battery low 21 VDC ±2 %

Inverse-polarity protection / input

Fuse 7.5 A (must be provided on-site by customer)

Inverse-polarity protection / battery

Fuse 7.5 A (at battery pack BP-2425)

Software (optional)

UPS software RUPS2000 OEM, for all established operating systems

LED display

3 colour LED connector for: Power ok (green) / Power Fail (orange) / Battery Low (red / orange flashing) / Battery defect (red / green flashing)

Battery capacitance

24 V / 2.5 Ah, recommended Battery pack , BP-2425 or BP-2425C

Battery monitoring

Battery test is carried out every 10 minutes in normal mode

Shutdown-Suppression

The Shutdown signal is disabled for about two minutes after startup, because a possible interface test of Windows® combined with a mains failure at the same time would switch the module off.

Reboot function

If DC IN fails and main power returns during shutdown mode of Windows®, the operating system will ‘lock’ with the message “Your PC is now safe”. The reboot function restarts the system after about 5 seconds (operator intervention not required).

Power consumption

App. 100 mA

Optional accessories

Article-No.

Designation

BP-2425-05 Battery pack 24 V / 2.5 Ah, -30…+70 °C link to the product
BP-2412A Battery pack, 24 VDC/1.2 Ah / 0…+40 °C link to the product
RUPS 2000 OEM UPS software bundle link to the product