IUPS-501
500 VA
- Integrated UPS
- Communications interface
- Temperature controlled
Other than conventional uninterruptable power supplies the IUPS-501 was designed to be installed into a PC. Thus, UPS and PC become one compact space-saving unit. The IUPS-501 as well as the additional battery pack can easily be installed into a drive slot and its handling is exceptionally user-friendly. Via interface and the UPS management software “RUPS 2000 OEM” the computer will be shut down and switched off in case of mains power failure.
| Technical data |
|
|---|---|
| Output power |
500 VA / 300 W with additional battery |
| Input voltage |
230 VAC ±15 % |
| Input frequency |
50 Hz ±5 % |
| Output voltage |
230 VAC ±15 % |
| Output frequency |
50 Hz ±1 % |
| Charging time |
10…12 h |
| Wave form |
Rectangular |
| Power factor |
0.6 |
| Overload protection |
UPS mode: switch off / mains mode: fuse |
| Transfer time |
<4 ms |
| Back up time |
100 W / 166 VA load app. 24 minutes |
| Interface |
DSUB 9-pole for UPS management software |
| Type of battery |
Lead-acid battery (VRLA) |
| Safety / EMC |
CE |
| Operating temperature |
0…+40 °C |
| Storage temperature |
0…+40 °C |
| Dimensions |
41.5 x 146 x 248 mm ±0.8 mm, additional battery 39 x 146 x 203 mm ±0.8 mm |
| Weight (net) |
2.75 kg, additional battery 2.55 kg |
| Product-specific data |
|---|
| Battery |
2 x 6 V / 3 Ah maintenance-free lead-acid batteries (VRLA) |
| Noise development |
<35 dbA |
| Load sensor |
Switch off at <20 Watt |
| Status display |
Mains mode: LED green |
| Acoustic alarms |
Power failure, every 5 seconds |
| Test function |
Test button at the front panel to check UPS function |
During storage the IUPS-501 has to be charged every 6 months.
| Optional accessories | ||
Article-No. |
Designation |
|
|---|---|---|
| RUPS 2000 OEM | UPS software bundle | link to the product |