You are here: Bicker Elektronik / Products / UPS systems / Special Equipment / TwinUPS 152410

TwinUPS 152410

1500 VA

  • 230 VAC AND +24 VDC output
  • Online technology (VFI-SS-111) with PFC
  • Widerange input voltage

The Twin UPS provides two separate voltages at the output. One is a sine AC voltage with 230 V / 50 or 60 Hz that is independent of the mains supply and the other is a 24 VDC voltage. In case of mains power failure both voltages are buffered. The TwinUPS can be applied in mechanical as well plant engineering and operates on the online principle using a sine inverter. Units with different output powers and voltages are available on request.

Technical data

 

Output power

1500 VA, 1050 W

Back up time

Only 230 VAC
100 % load, 5 min. / 80 % load, 7 min. / 50 % load, 15 min.

 

Only 24 VDC
100 % load, 25 min. / 80 % load , 30 min. / 50 % load, 50 min.

Overload protection

Switch off with auto-recovery

Charging time

App. 4 h charged up to 80 %

 

Input

 

Input voltage range

160…276 VAC at 100 % load

Derating

70 % load at 140…159 VAC, 40 % load at 120…139 VAC

Input frequency range

50 or 60 Hz ±3 Hz (automatic frequency recognition)

Input current with charged batteries

5.7 A

Input current

8 A (at rated load, minimum input voltage and battery charging)

Inrush current behaviour

Softstart

Power factor (cos j)

>0.97

 

Output AC

 

Output voltage

AC: 230 VAC, adjustable 208, 220, 230, 240 VAC

Output frequency

50 / 60 Hz ±0.5 %

Output voltage tolerance

±2 %

Efficiency at rated load

>90 %

Overload

125 % for 1 min., 150 % for 10 sec.

Short circuit protection UPS

Switch off of UPS or fuse at input line

Wave form in UPS mode

Sine wave

Power factor

0.7

 

Output DC

 

Output voltage

DC: 24 VDC / 10 A, other voltages and powers on request

Overvoltage protection

Switch off at +26 V…31 V

Short circuit protection

Switch off with auto-recovery

Load regulation

±1 %, load step ±40 % related to 60 % load

 

Bypass

 

Voltage tolerance

160…276 VAC

Frequency tolerance

±5 Hz

Product-specific data

Interface

 

Sub-D 9 Pin female

RS232 interface and potential-free contacts (open collector), mains failure and battery low

USB

Standard 1.1

EPO

External emergency cutout of output via break contact

 

Battery

 

Type of battery

Lead-gel battery, closed and maintenance-free

Nominal voltage

36 V

Number of 12 V blocks

3 pcs.

Nominal capacitance

9 Ah

Charging voltage

41 V

Charging current

1.5 A

Battery test

Automatically, once a month

 

General data

 

Chassis material

Sheet steel / front plastic

Chassis colour

Light grey / yellow

Ingress protection

IP 21

Operating humidity

0…95 % RH, non-condensing

Operating temperature

0…+40 °C

Dimensions

310 x 155 x 420 mm ±1 mm

Weight (net)

22 kg

The service life of the batteries is app. 4…5 years at +20 °C and will decrease by half with each temperature increase of 10 °C according to EUROBAT.
During storage the UPS has to be charged at least every 6 months.

Technical documentation: