TwinUPS 152410
1500 VA
- 230 VAC AND +24 VDC output
- Online technology (VFI-SS-111) with PFC
- Widerange input voltage
The Twin UPS provides two separate voltages at the output. One is a sine AC voltage with 230 V / 50 or 60 Hz that is independent of the mains supply and the other is a 24 VDC voltage. In case of mains power failure both voltages are buffered. The TwinUPS can be applied in mechanical as well plant engineering and operates on the online principle using a sine inverter. Units with different output powers and voltages are available on request.
| Technical data |
|
|---|---|
| Output power |
1500 VA, 1050 W |
| Back up time |
Only 230 VAC |
|
Only 24 VDC |
|
| Overload protection |
Switch off with auto-recovery |
| Charging time |
App. 4 h charged up to 80 % |
| Input |
|
| Input voltage range |
160…276 VAC at 100 % load |
| Derating |
70 % load at 140…159 VAC, 40 % load at 120…139 VAC |
| Input frequency range |
50 or 60 Hz ±3 Hz (automatic frequency recognition) |
| Input current with charged batteries |
5.7 A |
| Input current |
8 A (at rated load, minimum input voltage and battery charging) |
| Inrush current behaviour |
Softstart |
| Power factor (cos j) |
>0.97 |
| Output AC |
|
| Output voltage |
AC: 230 VAC, adjustable 208, 220, 230, 240 VAC |
| Output frequency |
50 / 60 Hz ±0.5 % |
| Output voltage tolerance |
±2 % |
| Efficiency at rated load |
>90 % |
| Overload |
125 % for 1 min., 150 % for 10 sec. |
| Short circuit protection UPS |
Switch off of UPS or fuse at input line |
| Wave form in UPS mode |
Sine wave |
| Power factor |
0.7 |
| Output DC |
|
| Output voltage |
DC: 24 VDC / 10 A, other voltages and powers on request |
| Overvoltage protection |
Switch off at +26 V…31 V |
| Short circuit protection |
Switch off with auto-recovery |
| Load regulation |
±1 %, load step ±40 % related to 60 % load |
| Bypass |
|
| Voltage tolerance |
160…276 VAC |
| Frequency tolerance |
±5 Hz |
| Product-specific data |
|---|
| Interface |
|
| Sub-D 9 Pin female |
RS232 interface and potential-free contacts (open collector), mains failure and battery low |
| USB |
Standard 1.1 |
| EPO |
External emergency cutout of output via break contact |
| Battery |
|
| Type of battery |
Lead-gel battery, closed and maintenance-free |
| Nominal voltage |
36 V |
| Number of 12 V blocks |
3 pcs. |
| Nominal capacitance |
9 Ah |
| Charging voltage |
41 V |
| Charging current |
1.5 A |
| Battery test |
Automatically, once a month |
| General data |
|
| Chassis material |
Sheet steel / front plastic |
| Chassis colour |
Light grey / yellow |
| Ingress protection |
IP 21 |
| Operating humidity |
0…95 % RH, non-condensing |
| Operating temperature |
0…+40 °C |
| Dimensions |
310 x 155 x 420 mm ±1 mm |
| Weight (net) |
22 kg |
The service life of the batteries is app. 4…5 years at +20 °C and will decrease by half with each temperature increase of 10 °C according to EUROBAT.
During storage the UPS has to be charged at least every 6 months.