IUPS-401-B1
400 VA
- Integrated UPS
- Communication interface
- Reboot function
Other than conventional uninterruptable power supplies the IUPS-401-B1 was designed to be installed into a PC. Thus, UPS and PC become one compact space-saving unit. The IUPS-401-B1 can easily be installed into a drive slot and its handling is exceptionally user-friendly. Via interface and the UPS management software “RUPS 2000” the computer will be shut down and switched off in case of mains power failure.
| Technical data |
|
|---|---|
| Output power |
400 VA / 240 W |
| Input voltage |
230 V AC ±15 % |
| Input frequency |
50 / 60 Hz ±5 % |
| Output voltage |
230 V AC ±15 % |
| Output frequency |
50 / 60 Hz ±1 % |
| Charging time |
App. 8 h (90 % load) |
| UPS Classification / Wave form |
VFD / rectangular |
| Protection |
Overload protection: UPS mode: 100…120 %, alarm / 120…190 %, switch off |
| Transfer time |
<6 ms |
| Back up time |
100 W / 166 VA load app. 5 minutes 180 W / 300 VA load app. 2…3 minutes |
| Interface |
Open collector for UPS management software |
| Safety / EMC |
EN62040-1-1 / CE / EN62040-2 |
| Operating temperature |
0…+40 °C |
| Storage temperature |
-15…+55 °C |
| Dimensions (WxDxH) |
146 x 253 x 42 mm ±0.5 mm |
| Weight (net) |
2.75 kg |
| Product-specific data |
|---|
| Transfer limit in mains / UPS mode |
190 V AC ±5 % |
| Transfer limit into UPS mode in case of overvoltage at the input |
248 V AC ±5 % |
| Type of battery |
2 x 6 V / 3 Ah, maintenance-free lead-gel batteries (VRLA) |
| Noise development |
<35 dbA |
| Load sensor |
Switch off at <20 Watt |
| Button |
To switch off alarm sound press for app. 1 second |
| Reboot function |
If mains voltage returns after a power failure while Windows® is already shutting down, the UPS switches the PC off (after the shut-down period) and switches it on again after approximately 5 seconds in conjunction with RUPS 2000 and an ACPI-PC (observe BIOS settings of mainboard). |
During storage the UPS has to be charged at least every 6 months.