You are here: Bicker Elektronik / Products / UPS systems / Integrated UPS / IUPS-401-B1

IUPS-401-B1

400 VA

  • Integrated UPS
  • Communication interface
  • Reboot function

Other than conventional uninterruptable power supplies the IUPS-401-B1 was designed to be installed into a PC. Thus, UPS and PC become one compact space-saving unit. The IUPS-401-B1 can easily be installed into a drive slot and its handling is exceptionally user-friendly. Via interface and the UPS management software “RUPS 2000” the computer will be shut down and switched off in case of mains power failure.

Technical data

 

Output power

400 VA / 240 W

Input voltage

230 V AC ±15 %

Input frequency

50 / 60 Hz ±5 %

Output voltage

230 V AC ±15 %

Output frequency

50 / 60 Hz ±1 %

Charging time

App. 8 h (90 % load)

UPS Classification / Wave form

VFD / rectangular

Protection

Overload protection: UPS mode: 100…120 %, alarm / 120…190 %, switch off
      Mains mode: fuse
Overtemperature protection: switch off

Transfer time

<6 ms

Back up time

100 W / 166 VA load app. 5 minutes     180 W / 300 VA load app. 2…3 minutes

Interface

Open collector for UPS management software

Safety / EMC

EN62040-1-1 / CE / EN62040-2

Operating temperature

0…+40 °C

Storage temperature

-15…+55 °C

Dimensions (WxDxH)

146 x 253 x 42 mm ±0.5 mm

Weight (net)

2.75 kg

Product-specific data

Transfer limit in mains / UPS mode

190 V AC ±5 %

Transfer limit into UPS mode in case of overvoltage at the input

248 V AC ±5 %

Type of battery

2 x 6 V / 3 Ah, maintenance-free lead-gel batteries (VRLA)

Noise development

<35 dbA

Load sensor

Switch off at <20 Watt

Button

To switch off alarm sound press for app. 1 second
To switch off UPS press for app. 4 seconds
To switch on UPS (cold start, without mains supply) press for app. 2 seconds

Reboot function

If mains voltage returns after a power failure while Windows® is already shutting down, the UPS switches the PC off (after the shut-down period) and switches it on again after approximately 5 seconds in conjunction with RUPS 2000 and an ACPI-PC (observe BIOS settings of mainboard).

During storage the UPS has to be charged at least every 6 months.

Technical documentation: