UPSI-2402-IP-CY
24 VDC/5 A
- Temperature range from -30…+70 °C
- Protection class IP67
- Robust aluminium casing
The new DC-UPS UPSI-2402-IP-CY has been designed for outdoor use. The μC-controlled DC-UPS is equipped with various protective functions and a battery control. The CYCLON cells used are characterized by a very broad operating temperature range. The CYCLON cells have a lifetime of up to 15 years which is a multiple of that of conventional lead-gel batteries. Additionally, the UPSI-2402-IP-CY is equipped with a load sensor and a timer function.
| Technical data |
|
|---|---|
| Input voltage |
24 V DC (22.5…30 V) |
| Input current |
5.5 A max. |
| Output voltage |
In normal mode: app. 0.5 V below input voltage |
| Output current |
5 A max. |
| Battery charge current |
0.4 A max. (internal battery charger) |
| Charging method |
UI characteristic, with temperature regulation |
| Protection |
Deep discharge protection: 19 V DC ±2 % |
| Transfer time / limits |
Mains / battery 20 V DC ±2 %, Battery / mains 22 V DC ±2 % |
| Interface |
DSUB9 connector, female (at interface cable) |
| Type of battery |
Equipped CYCLON cells, maintenance-free, 12 V / 2.5 Ah |
| Safety / EMC |
CE |
| Operating temperature |
-30…+70 °C |
| Storage temperature |
-40…+80 °C |
| Storage humidity |
0…95 % RH, non-condensing |
| Dimensions (WxDxH) |
160 x 258.5 x 85 ±0.5 mm |
| Weight (net) |
2.7 kg |
| Product-specific data |
|---|
| Battery monitoring |
Battery test is carried out in normal mode approx every 10 minutes (optional sginaling contact) |
| Power consumption |
App. 50 mA |
| Shutdown suppression |
During system start-up the shutdown signal is suppressed for app. 2 minutes. |
| Reboot function |
If power fails and then returns during the shutdown mode of Windows®, the operating system will ‚lock‘ with the message „Your PC is now safe“. The reboot function restarts the system after about 10 seconds. |
| Load sensor |
Switch-off in UPS mode <10 Watt |
| Timer function |
2 min – 6 min – 20 min – off, adjustable via DIP switch |
| Back up time |
App. 1h 45 min at 1 A / app. 30 min at 3 A / app. 15 min at 5 A (measured at +21 °C) |
| Optional accessories | ||
Article-No. |
Designation |
|
|---|---|---|
| RUPS 2000-B1 | UPS Management Software (CD-ROM) | link to the product |