BP-2450C
24 V/5 Ah
- Temperature range -30…+70 °C
- Service life up to 15 years
- Temperature sensor
The high-quality battery pack BP-2450C serves to store energy for DC UPS models of the UPSI-B-24xx series. The equipped CYCLON cells are distinguished by their wide ambient operating temperature range from -30…+70 °C. The service life of CYCLON cells with up to 15 years is considerably higher as compared to conventional lead-acid batteries. To ensure maximal performance the charging voltage is controlled by a temperature sensor.
| Technical data |
|
|---|---|
| Nominal voltage |
24 VDC |
| Capacitance |
5 Ah |
| Number of batteries |
12 cells à 2 V |
| Type of battery |
Maintenance-free CYCLON batteries |
| Life cycles |
10 000…300 depending on ambient temperature, charge and discharge |
| Fuse |
50 A, circuit breaker |
| Operating temperature |
-30…+70 °C |
| Storage temperature |
-30…+70 °C |
| Temperature sensor |
For use with UPSI-B-24xx series |
| Dimensions |
268 x 102 x 140 mm, ±0.5mm |
| Weight (net) |
6.7 kg |
| Back up time measured at +21 °C by means of UPSI-B-2410 |
|||
|---|---|---|---|
| Discharge current |
1 A |
5 A |
10 A |
| Time app. |
4 h 50 min |
48 min |
21 min |
The Back up time depends on battery capacity, load and ambient temperature.